Abstract
This article studies the problem of fundamental frequency positive-sequence component separation in unbalanced three-phase systems for grid-integration applications. We propose a-simple-to-implement approach involving a modified delayed signal cancellation method and moving average filtering. A delay-based linear-regression framework is considered to make the sequence component separation frequency-adaptive, providing fast and accurate frequency estimation. Comparative experimental results demonstrate the suitability of the proposed method over conventional approaches.
| Original language | English |
|---|---|
| Pages (from-to) | 357-363 |
| Journal | Energy Reports |
| Volume | 8 |
| Issue number | November 2022 |
| Early online date | 22 Oct 2022 |
| DOIs | |